Series 67 and 767
Low Water Cut-Offs
For Steam Boilers
Before using this product read and understand instructions.
Save these instructions for future reference.
All work must be performed by qualified personnel trained in the proper application, instal-
lation, and maintenance of plumbing, steam, and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.
To prevent electrical shock, turn off the electrical power before making electrical connections.
This low water cut-off must be installed in series with all other limit and operating controls
installed on the boiler. After installation, check for proper operation of all of the limit and
operating controls, before leaving the site.
We recommend that secondary (redundant) Low Water Cut-Off controls be installed on all
steam boilers with heat input greater than 400,000 BTU/hour or operating above 15 psi
steam pressure. At least two controls should be connected in series with the burner
control circuit to provide safety redundancy protection should the boiler experience a
low-water condition. Moreover, at each annual outage, the low water cutoffs should be
dismantled, inspected, cleaned, and checked for proper calibration and performance.
To prevent serious personal injury from steam and hot water make sure there is a discharge
line from the blow down valve to a proper place of disposal.
To prevent a fire, do not use this low water cut-off to switch currents over 7.4A, 1/3 Hp at
120 VAC or 3.7A, 1/3 Hp at 240 VAC, unless a starter or relay is used in conjunction with it.
Failure to follow this warning could cause property damage, personal injury or death.
WARNING
CAUTION
!
WARNING
Series 67
Series 767
®
Applications:
For residential and commercial boilers of
any steaming capacity.
McDonnell & Miller
Installation & Maintenance
Instructions
MM-201(E)
Vue de la page 0
1 2 3 4 5 6 ... 11 12

Résumé du contenu

Page 1 - McDonnell & Miller

Series 67 and 767Low Water Cut-OffsFor Steam Boilers• Before using this product read and understand instructions.• Save these instructions for future

Page 2 - OPERATION

NOTE: To connect wires to the terminalson the burner, or low water cut-off, placethe bare end of the wire under the terminalscrew and tighten the scre

Page 3 - STEP 2 - Preparation

For the 24V Burner/24V Feeder setups.BURNER101A-24120 VACSUPPLY24V TRANSFORMER(101-24V-48)1234NH24V69c. Connect the "hot" wire from the boil

Page 4 - 2 (13mm) NPT

MAINTENANCESCHEDULE:• Blow down weekly (at least once) when the boiler is in operation.• Disassemble and inspect annually. Replace the low water cut-o

Page 5

AD2INSTALLATION –TOOLS NEEDED:One (1) tube cutter, one (1) pencil, one (1) flatheadscrewdriver, one (1) adjustable wrench and two (2)pipe wrenches.The

Page 6 - For Series 767

3a. Turn the boiler off.b. Drain the water in the boiler to a level whichis below the lower gauge glass tapping (B)of the control body (A). Allow the

Page 7

c. Using an adjustable wrench, install a a"(9.5mm) NPT compression fitting base (K)to the upper tapping (L) in the control (A).Tighten to 31 ft•l

Page 8 - STEP 4 - Electrical Wiring

h. Insert the tubing (Q) into the upper compres-sion fitting (U) and tighten the fitting to 31 ft•lb(42 N•m).UQg. Position the tubing (Q) next to the

Page 9

k. Using two (2) pipe wrenches, rotate the uppertee (P) clockwise and the lower tee (J) counter-clockwise so that the end of the tube can beinserted i

Page 10

7TUAWc. Using a pipe wrench, install a w" (19mm) NPTpipe (T) into the opening of the blow downvalve (U) and tighten to 47 ft•lb (64 N•m).Ab. Inst

Page 11 - Wiring Alternative

8STEP 4 - Electrical Wiringa. Using a flathead screwdriver, remove the one(1) screw that secures the low water cut-offswitch cover (Y).• To prevent el

Page 12

9NOTE: To connect wires to the terminalson the water feeder, burner, or low watercut-off, place the bare end of the wireunder the terminal screw and t