Crown Boiler BWC150 Spécifications

Naviguer en ligne ou télécharger Spécifications pour Chauffe-eau et chaudières Crown Boiler BWC150. Crown Boiler BWC150 Specifications Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 73
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
BWC Series


INSTALLATION INSTRUCTIONS


BWC150
BWC225
: Improper installation, adjustment, alteration,
service or maintenance can cause property damage, injury,
or loss of life. For assistance or additional information, con-
sult a qualied installer, service agency or the gas supplier.
This boiler requires a special venting system. Read these
instructions carefully before installing.
D ESIGNED TO L EAD
Manufacturer of Hydronic Heating Products
P.O. Box 14818 3633 I. Street
Philadelphia, PA 19134
www.crownboiler.com
Vue de la page 0
1 2 3 4 5 6 ... 72 73

Résumé du contenu

Page 1 - BWC Series

BWC Series   INSTALLATION INSTRUCTIONS 

Page 2

83) Minimum Vent and Air Intake Lengths - Minimum vent length is 2ft. Minimum air inlet length is 2ft.4) Permitted Terminals for Horizontal Venti

Page 3

9TABLE 6.2a: SUMMARY OF HORIZONTAL VENTING OPTIONS VENT OPTION # 1 2 3 4 5CLASSIFICATION USED IN THIS MANUALHORIZONTAL DIRECT VENTHORIZONTAL DIRECT V

Page 4 - II Specications

10FIGURE 6.3a: LOCATION OF VENT TERMINAL RELATIVE TO WINDOWS, DOORS, GRADEFIGURE 6.3b: LOCATION OF VENT TERMINAL RELATIVE TO METERS AND FORCED AIR I

Page 5 - IV Locating the Boiler

116) Permitted Terminals for Vertical Venting (Vent Options 6, 7) - A rodent screen is installed in the end of the vent pipe. Vent manufacturer par

Page 6

12TABLE 6.2b: SUMMARY OF VERTICAL VENTING OPTIONS VENT OPTION # 6 7CLASSIFICATION USED IN THIS MANUALVERTICALDIRECT VENTVERTICAL DIRECT VENTILLUSTRATE

Page 7 - V Air for Ventilation

13TABLE 6.5: PERMISSIBLE VENT SYSTEMS AND PRINCIPLE VENT COMPONENTSMANUFACTURER VENT SYSTEM SIZEWALL THIMBLESHORIZONTAL TERMINATIONVERTICAL TERMINATIO

Page 8

14 Read this only if the BWC boiler is replacing an existing boiler that is being removed from a common chimney. This section does not apply

Page 9 - VI Venting

15 3) Assembly of Metal-Fab Corr/Guard Vent System: a) Corr/Guard General Notes:• Do not cut Corr/Guard vent components.• Refer to Corr/Guard instal

Page 10

16FIGURE 6.8: Z-VENT III CONNECTION TO VENT COLLAR 3) Assembly of Z-Flex Z-Vent III: a) General Notes: • Non-expanded ends of SVE Serie

Page 11

17 4) Assembly of Heat Fab Saf-T Vent EZ Seal: a) Saf-T Vent General Notes: These instructions cover the installation of Saf-T Vent EZ

Page 13

18 5) Assembly of Protech FasNSeal a) FasNSeal General Notes: • Do not cut 4” FasNSeal pipe. Consult FasNSeal instructions for method of

Page 14

19 d) 4” galvanized smoke pipe will t inside the inlet collar on the BWC boiler. Depending upon the exact OD of the pipe used, it may be

Page 15 - EQUIVALENT LENGTH

20PAGE INTENTIONALLYLEFT BLANK

Page 16

21PAGE INTENTIONALLYLEFT BLANK

Page 17

22PAGE INTENTIONALLYLEFT BLANK

Page 18

VII Gas PipingGas piping to the boiler must be sized to deliver adequate gas for the boiler to re at the nameplate input at an inlet pressure between

Page 19

VIII System PipingA. General System Piping PrecautionsTABLE 8.1: FLOW REQUIREMENTS THROUGH BOILERBOILER MODELMIN. REQUIRED FLOW (GPM)MAX. ALLOWABLE F

Page 20

Method 1: Primary/Secondary Piping - Boiler in Secondary Loop This method can be used in heat-only applications as shown in Figure 8.2 or with an i

Page 21

Figure 8.2: Piping Method #1 - Heat OnlyCalculate total equivalent length from Table 8.7: 20 Straight Pipe + 6 Elbows x 3.75 + 2 Turns in Tees x 8 +

Page 22 - INTENTIONALLY

Figure 8.3: Piping Method #1 - Heat + Indirect Water Heater 27

Page 23

Table of Contents I. Product Description 2 II. Specications 2 III. Before Installing 3 IV. Locating The Boiler 3 V

Page 24

Figure 8.4b: Piping Method #1 - Indirect Water Heater Loop Piping (Shaded)Figure 8.4a: Piping Method #1 - Secondary Loop Piping (Shaded)28

Page 25 - VII Gas Piping

29TABLE 8.7: FITTING EQUIVALENT LENGTHSFITTINGPIPE SIZE EQUIVALENT LENGTH (ft)90 ELBOW 1 1/4 3.75TURN IN TEE 1 1/4 8.00RUN OF TEE 1 1/4 2.50SWING CHE

Page 26 - VIII System Piping

30Figure 8.8: Piping Method #2 - Direct Connection of Boiler to Heating System Method 2: Direct Connection to Heating System (Generally NOT Recommend

Page 27

31C: Standard Piping Installation Requirements Observe the following guidelines when making the actual installation of the boiler piping:1) The rel

Page 28

323) The return piping may be connected into the boiler through the back or sides of the boiler by rotating the drain elbow and routing the return pi

Page 29

33Figure 8.11: Chiller PipingFigure 8.10: Isolation of the Boiler From Oxygenated Water with A Plate Heat Exchanger

Page 30

34IX Wiring 1) Line Voltage (120 VAC) Connections (Fig 9.1) – The line voltage connections are located in the juncti

Page 31

Figure 9.1: Wiring Connections Diagram35

Page 32

Figure 9.2: Ladder Diagram36

Page 33 - 

Figure 9.3: Wiring of Isolation Relay for Control of Two Heating Circulators 37

Page 34

2I Product DescriptionThe BWC is an aluminum gas red condensing boiler designed for use in forced hot water heating systems requir-ing supply water

Page 35 - Figure 8.11: Chiller Piping

X Start-up and CheckoutUse the following procedure for initial start-up of the boiler:1) If not already done, ush the system to remove sediment, ux

Page 36 - IX Wiring

WATER QUALITY AND BOILER WATER ADDITIVESIMPORTANT NOTEThis boiler is equipped with an aluminum heat exchanger that can be seriously damaged by failure

Page 37

      

Page 38 - Figure 9.2: Ladder Diagram

417) Start the boiler using the lighting instructions on page 39. After the boiler is powered up, it should go through the following sequence. Sequ

Page 39

42Figure 10.2a: Honeywell Gas Valve Detail11) Perform a combustion test. On horizontally vented units, the sample probe may be inserted into the ter

Page 40 - X Start-up and Checkout

Table 10.3: Typical Sea Level CO2/O2 Combustion WARNINGEACH BWC SERIES BOILER IS TESTED AT THE FACTORY AND ADJUSTMENTS TO THE AIR-FUEL MIXTURE ARE NO

Page 41

XI Operation1) The BWC boiler uses a microprocessor based control, known as a “MCBA”, to manage all boiler functions including ame supervision a

Page 42 - 

45 In standby mode, it is possible to view both the heating supply set point temperature and the “domestic hot water reference set point”. The “do

Page 43

USE MODE KEY TO TOGGLE BETWEEN MODES(Mode returns to Standby from other modes if no key is pressed for 20 min.)

Page 44

47 3) Two basic types of errors codes are shown on the display: • Soft Lockout Codes – When a soft lockout occurs, the boiler will shut down

Page 45

III Before Installing1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance w

Page 46 - XI Operation

Figure 11.4: Outdoor Reset Curve487) The sequence of operation for a BWC series boiler on a call for heat from a thermostat is as described below:

Page 47

XII. Service and MaintenanceIMPORTANTWARRANTY DOES NOT COVER BOILER DAMAGE OR MALUFUNCTION IF THE FOL-LOWING STEPS ARE NOT PERFORMED AT THE INTERVALS

Page 48 - 

d. Remove the ignition electrode and inspect it for oxides. Clean the oxides off the electrode with sandpaper. Inspect the ceramic insulator

Page 49 - Table 11.3: Boiler Status

51XIII. TroubleshootingA. Troubleshooting problems where no error code is displayed:CONDITION POSSIBLE CAUSESDisplay Blank, Fan off, LWCO lights off

Page 50

52B. Trouble shooting problems where a soft lockout code is displayed. When a soft lockout occurs, the boiler will shut down and the display will

Page 51 - XII. Service and Maintenance

53C. Trouble shooting problems where a hard lockout code is displayed. When a hard lockout occurs, the boiler will shut down and the display wil

Page 52

54PAGE INTENTIONALLYLEFT BLANK

Page 53 - XIII. Troubleshooting

55XIV PartsThe following parts may be obtained from any Crown distributor. To nd the closest Crown distributor, consult the area Crown representativ

Page 54

56BWC REPLACEMENT PARTS LISTKEY DESCRIPTIONBWC150 BWC225CROWN PART #QUANTITYCROWN PART #QUANTITY1 Crown Aluminum Nameplate 98-004 1 98-004 12 Aluminum

Page 55 - display

57BWC REPLACEMENT PARTS LISTKEY DESCRIPTIONBWC150 BWC225CROWN PART #QUANTITYCROWN PART #QUANTITY47 Nylon Glide Foot 1”Dia x 3/4” Long 700111 4 700111

Page 56

4Figure 4.1: Clearances To Combustible Or Non-combustible MaterialTable 4.2: Clearances From Vent Piping To Combustible ConstructionTYPE OF VENT PIPE

Page 60

61Gas Train Assembly (Honeywell Valve)

Page 61

Gas Train Assembly (Dungs Valve)62

Page 62

63BWC REPLACEMENT PARTS LISTKEY DESCRIPTIONBWC150 BWC225CROWN PART #QUANTITYCROWN PART #QUANTITY89 #6-32 x 13mm Hex x 92mm, Long Standoff 900711 2 900

Page 64

BWC REPLACEMENT PARTS LISTKEY DESCRIPTIONBWC150 BWC225CROWN PART #QUANTITYCROWN PART #QUANTITY140 3 x 63mm O-Ring 230003 1 NA 1141 Fan Inlet Block 230

Page 67

V Air for Ventilation Air for combustion must always be obtained directly from outdoors, however sufcient air for ventilation must still be provid

Page 69

69Appendix A: Special Requirements For Side-Wall Vented AppliancesIn The Commonwealth of MassachusettsIMPORTANTThe Commonwealth of Massachusetts requ

Page 71

PN: 980040 Rev. 6BWC - 12/12Manufacturer of Hydronic Heating ProductsP.O. Box 14818 3633 I. StreetPhiladelphia, PA 19134www.crownboiler.com

Page 72

6Figure 5.1: Boiler Installed In A Conned Space, Ventilation Air From Inside• If the total volume of both the boiler room and the room to which the

Page 73 - Philadelphia, PA 19134

7VI VentingWARNINGFailure to vent this boiler in accordance with these instructions could result in unreliable boiler operation, severe damage to the

Commentaires sur ces manuels

Pas de commentaire