WARNING This conversion kit shall be installed by a qualied service agency in accordance with the manufacturer’s instructions and all applicable co
In addition to these instructions, this kit consists of the following items:Part Number Description Color980236 Natural to LP Conversion Label She
Figure 1a: Dungs “HO” Gas Valve Detail (BWC070, BWC090, BWC120, BWC151)Figure 1b: Dungs “RH” Gas Valve Detail (BWC150)Figure 2: Honeywell VK8115Gas Va
Table 2: Number of Throttle TurnsBoiler Model Gas ValveFull Turns at Various Altitudes0-2000ft 2000-5200ft 5200-7800ft 7800ft-10200ftBWC070 Dungs GB-W
45) Attempt to start the boiler using the lighting instructions located inside the lower front cover of the boiler. If the boiler doesnotlightont
59) Verify that the gas inlet pressure is between the upper and lower limits shown in Table 4 with all gas appliances (including the converted boiler