Because hot water is always circulated in the hot
water branch the entire branch should be insulated to
prevent excessive heat loss.
MANIFOLD DOMESTIC WATER PIP-
ING
Figure 7.10 illustrates the recommended method of
piping the domestic water side of several tanks to-
gether. All Mega-Stors are piped in a “reverse- return”
manner just like the boiler piping. This balances the
pressure drop through each tank, resulting in an even

Each tank must have its own T&P valve. It is recom-
mended that each tank be equipped with its own isola-
tion valves, unions, and drains so that one tank may
be removed from the system. If local codes require a
-

be used for tanks or each tank must be equipped with



is permitted, an expansion tank must be sized to ac-
commodate the expansion volume of all tanks.
TABLE 7.7: MINIMUM T&P VALVE SIZES
*If the Mega-Stor is connected to a boiler which has a Gross Output
LESS than the “Max. T&P Valve Capacity” shown below, install
a T&P valve having a capacity greater than or equal to the boilers
Gross Output.
*If the Mega-Stor is connected to a boiler which has a Gross Output
GREATER than the “Max. T&P Valve Capacity” shown below,
install a T&P valve having a capacity greater than or equal to the
“Max T&P Valve Capacity.”
Model Max T&P Valve Capacity (BTU/hr)
MS-26 172,800
MS-40 181,800
MS-53 199,800
MS-79 215,100
MS-119 445,635
MSH-40 103,344
MSH-53 145,289
*Maximum T&P valve pressure setting - 150 psi
FIGURE 7.6A: BASIC DOMESTIC WATER PIPING